Plan Review Notes
Plan Review Notes For Permit 04041693
Permit Number 04041693
Review Stop E
Sequence Number 1
Notes
Date Text
2004-05-06 00:00:00************NOTES/PROVISO ***********
  
 1)NOTE> MIN LOAD FOR RANGE TO BE 8KW,
 220.19.
  
 2)NOTE: MAX LOAD ON 1P20A CIRCUIT IS
 1.9 KW. WASHERAND IRRG PUMP SHOWN AS
 2KW.
  
 SD'S INSTALLED PER NFPA-72 8-1.4.2
  
 REVISE PLANS BEFORE ROUGH.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.