Plan Review Notes For Permit 04041688 |
Permit Number |
04041688 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-05-04 00:00:00 | ***** RDLINED/ PROVISO ********** | | | | REVISE PLANS BEFORE ROUGH. | | | | 1)NOTE: PLEASE SEE 220.19, MIN KW LOAD | | FOR RANGE IS 8KW FOR LOAD CALCS., | | | | 2)NOTE : MAX KW LOAD FOR A 1-P20A | | BRANCH CIRCUIT IS 1.9 KW. | | SHOWN AS 2KW FOR IRRG PUMP AND WASHER. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|