2004-05-06 00:00:00****** REDLINED / PROVISO *********
  
 REVISE PLANS BEFORE ROUGH.
  
 1)NOTE: PLEASE SEE MAX LOAD FOR 1P20A
 CIRCUIT IS 1.9 KW. IRRG PUMP, WASHER
 ARE BOTH SHOWN AT 2KW.
  
 2)NOTE: PLEASE SEE MIN LOAD FOR RANGE
 IS 8KW, 220.19
  
 SD'S TO BE INSTALLED PER NFPA-72 8-1.4.2
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  