Plan Review Notes
Plan Review Notes For Permit 04041665
Permit Number 04041665
Review Stop E
Sequence Number 1
Notes
Date Text
2004-05-03 00:00:00***** REDLINED / PROVISO *********
  
 1)NOTE: PLEASE SEE 220.19 FOR A MIN OF
 8KW TO BE FIGURED FOR LOAD CALCS.
  
 2)NOTE: MAX LOADS ON 1-POLE 20A CIRCUITS
 IS 1.9 KW. IRRG PUMP AND WASHER SHOWN
 AT 2KW.
  
 SD'S TO BE INSTALLED PER NFPA-72 8-1.4.2
  
 REVISE PLANS BEFORE ROUGH.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  