Plan Review Notes For Permit 04041658 |
Permit Number |
04041658 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-05-20 00:00:00 | BUILDING REVIEW PROVISO: | | 1-PROVIDE COPIES OF GARAGE DOORS DWGS | | THAT WERE PRESENTED TO SBCCI FOR | | APPROVAL. NEED DWGS WITH THE SAME DATE | | THEY WERE SIGNED AND SEALED AS NOTED | | ON SBCCI EVALUATION REPORT. | | 2-DETAIL E/4 AND RESIDENTIAL NOTES ON | | SHEET #2 DON'T MATCH. CLARIFY FASTENER | | SPACING. SEC. 104.2.1.2 OF CITY | | AMENDMENTS TO FBC 2001. | | 3-SECTION A/4: SPECIFY WHERE ARE TABLES | | 6 AND 8 FOR ROOF TILE FASTENER TAKEN | | FROM. SEC. 104.2.1.1 CITY AMENDMENTS | | TO FBC 2001. | | 4-FLOOD ZONE AO: NEED TO PROVIDE THE | | ELEVATION CERTIFICATE. |
|