Plan Review Notes For Permit 04041650 |
Permit Number |
04041650 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-05-06 00:00:00 | ***** PROVISO/ REDLINED*************** | | | | 1)NOTE: PLEASE SEE MIN LOAD FOR RANGE | | TO BE 8KW PER 220.19 | | | | 2)NOTE: MAX LOAD FOR 1-P20A CIRCUIT IS | | 1.9KW. WASHER/IRRG PUMP SHOWN AS 2KW | | | | SD'S TO BE INSTALLED PER NFPA-72 8-1.4.2 | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 |
|