Plan Review Notes
Plan Review Notes For Permit 04041650
Permit Number 04041650
Review Stop E
Sequence Number 1
Notes
Date Text
2004-05-06 00:00:00***** PROVISO/ REDLINED***************
  
 1)NOTE: PLEASE SEE MIN LOAD FOR RANGE
 TO BE 8KW PER 220.19
  
 2)NOTE: MAX LOAD FOR 1-P20A CIRCUIT IS
 1.9KW. WASHER/IRRG PUMP SHOWN AS 2KW
  
 SD'S TO BE INSTALLED PER NFPA-72 8-1.4.2
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717