2004-05-03 00:00:00******** REDLINED/ PROVISO*******
  
 REVISE PLANS BEFORE ROUGH.
  
 1)NOTE: PLEASE SEE MIN LOAD FIGURED FOR
 RANGE TO BE 8KW PER 220.19. SHOWN AS
 7.5KW
  
 2)NOTE: MAX LOAD FOR 1-P 20A CIRCUITS
 1.9KW,80% IRRG PUMP,WASHER ARE SHOWN AS
 2KW
  
 SD'S PER NFPA-72 8-1.4.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  