2004-05-03 00:00:00**********REDLINED/PROVISO *******
  
 REVISE PLANS BEFORE ROUGH.
  
 1)NOTE: PLEASE SEE 220.19 FOR A MIN OF
 8KW FIG FOR RANGE LOAD.
 2)NOTE: MAX LOAD ON A 1-P20A CIRCUIT
 IS 1.9KW, IRRG PUMP AND WASHER SHONW AT
 2KW. EXCEEDS 80%.
 3)NOTE: PLEASE SEE NFPA-72 FOR SD PLACE-
 -MENT. 8.1.4.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  