Notes
Date Text
2004-05-03 00:00:00***** REDLINED/PROVISO *********
  
 REVISE PLANS BEFORE ROUGH.
  
 1)NOTE: PLEASE SEE 220.19. MIN LOAD FOR
 RANGE TO BE 8KW. SHOWN AS 7.5KW
  
 2)NOTE: MAX LOAD FOR 1-P20A CIRCUITS TO
 BE 1.9KW 80%. IRRG PUMP AND WASHER SHOWN
 AT 2KW.
  
 SD'S PER NFPA-72 8-1.4.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.