2004-05-03 00:00:00****** REDLINED/PROVISO ************
  
 1)NOTE: MIN LOAD TO BE FIGURED FOR RANGE
 IS 8KW PER 220.19, SHOWS 7.5KW
  
 2)NOTE: MAX LOAD OF 1.9KW (80%) FOR
 1-P20A CIRCUITS. IRRG PUMP, WASHER
 EACH SHOWN AS 2KW.
  
 SD'S TO BE INSTALLED PER NFPA-72 8-1.4.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.