2004-05-03 00:00:00******** REDLINED/ PROVSIO*********
  
 1)NOTE: PLEASE SEE RANGE LOAD SHOWN AT
 7.5KW, MIN PER 220.19 IS 8KW.
  
 2)NOTE: PLEASE SEE MAX LOADS FOR 1-P20A
 CIRCUITS IS 1.9KW,80%. IRRG PUMP,WASHER.
  
 SD'S PER NFPA-72 8-1.4.2
  
 REVISE PLANS BEFORE ROUGH.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  