Plan Review Notes
Plan Review Notes For Permit 04041572
Permit Number 04041572
Review Stop E
Sequence Number 1
Notes
Date Text
2004-05-04 00:00:00******** REDLINED/ PROVISO *******
  
 REVISE PLANS BEFORE ROUGH.
  
 1)NOTE: MIN LOAD FOR RANGE IS 8KW PER
 220-19, SHOWN AS 7.5KW.
  
 2)NOTE: MAX LOAD FOR A 1-POLE 20A CIR-\-
 CUIT IS 1.9KW. SHOWN AS 2KW, IRRAG PUMP,
 WASHER.
  
 SD'S NOTED TO BE INSTALLED PER NFPA-72
 8-1.4.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]