2004-05-03 00:00:00******* REDLINED /PROVISO **********
  
 1)NOTE: MIN KW FOR RANGE TO BE 8KW
 220.19
 2)NOTE: MAX LOA FOR 20A1-POLE CIRCUIT IS
 1.9 KW. IRRG PUMP AND WASHER IS SHOWN AS
 2KW
 SD'S INSTALLED PER NFPA-72 8-1.4.2
 SUBMIT REVISED PLANS BEFORE ROUGH.