Plan Review Notes
Plan Review Notes For Permit 04041495
Permit Number 04041495
Review Stop E
Sequence Number 1
Notes
Date Text
2004-05-03 00:00:00******* REDLINED/ PROVISO ********
  
 REVISE PLANS BEFORE ROUGH.
 MAX LOAD FOR 20A CIRCUIT(S), WASHER
 SHOWN AT 2KW, IRRG PUMP, 1-P20A, 2KW?
 MAX LOAD ALLOWED ON 20A CIR 1.9KW
  
 PLEASE SEE 220.19 FOR MIN OF 8KW FIG
 FOR RANGE LOAD.