Plan Review Notes For Permit 04041488 |
Permit Number |
04041488 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-05-03 00:00:00 | ************ REDLINED /PROVISO ****** | | | | REVISE PLANS BEFORE ROUGH. | | | | 1)NOTE: PLEASE SEE 220.19 FOR A MIN OF | | 8KW TO BE FIGURED FOR RANGE. SHOWS 7.5 | | | | 2)NOTE: PLEASE SEE MAX LOAD ON A 1-P20A | | CIRCUIT IS 1.9 KW, IRRG PUMP,WASHER | | SHOWN AT 2KW. | | | | SD'S TO BE INSTALLED PER NFPA-72 8-1.4.2 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|