2004-05-03 00:00:00************ REDLINED /PROVISO ******
  
 REVISE PLANS BEFORE ROUGH.
  
 1)NOTE: PLEASE SEE 220.19 FOR A MIN OF
 8KW TO BE FIGURED FOR RANGE. SHOWS 7.5
  
 2)NOTE: PLEASE SEE MAX LOAD ON A 1-P20A
 CIRCUIT IS 1.9 KW, IRRG PUMP,WASHER
 SHOWN AT 2KW.
  
 SD'S TO BE INSTALLED PER NFPA-72 8-1.4.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  