2004-05-27 00:00:00PROVISO:
 ORIGINAL PERMIT APPLICATION REQUIRED.
  
 PLEASE CONTACT CHIEF MECHANICAL
 INSPECTOR, HAROLD MOSER (805-6732) FOR A
 PRE-INSPECT, TRANSFERS MAY NOT BE
 REQUIRED.
  
 TRANSFER GRILLES ARE NOT SIZED PROPERLY.
 AS PER THE 2001 FBC(M) 601.4 EXCEPTION
 #2, A MINIMUM OF 50 SQ INCHES OF GRILLE
 AREA TO 100 CFM OF SUPPLY AIR WITH A 1"
 UNDERCUT OF THE DOOR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.