Plan Review Notes For Permit 04041478 |
Permit Number |
04041478 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-05-27 00:00:00 | PROVISO: | | ORIGINAL PERMIT APPLICATION REQUIRED. | | | | PLEASE CONTACT CHIEF MECHANICAL | | INSPECTOR, HAROLD MOSER (805-6732) FOR A | | PRE-INSPECT, TRANSFERS MAY NOT BE | | REQUIRED. | | | | TRANSFER GRILLES ARE NOT SIZED PROPERLY. | | AS PER THE 2001 FBC(M) 601.4 EXCEPTION | | #2, A MINIMUM OF 50 SQ INCHES OF GRILLE | | AREA TO 100 CFM OF SUPPLY AIR WITH A 1" | | UNDERCUT OF THE DOOR. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|