Plan Review Notes For Permit 04041478 |
Permit Number |
04041478 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-05-04 00:00:00 | DENIED: | | 1.PLEASE PROVIDE A COMPLETED FORM 600C | | OR ENERGY & MANUAL J CALCULATIONS AS | | REQUIRED PER 2001 FBC CHAPTER 13 SUB- | | CHAPTER 101.4.1.1 & 600.1.C. | | | | 2.PER THE REVISED 2001 FBC(M) 601.4 | | EFFECTIVE JUNE 30, 2003; BALANCED AIR | | REQUIRED.PLEASE SEE THE ATTACHED | | SCHEDULE FOR PROPER SIZING. | | | | 3.AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|