Plan Review Notes
Plan Review Notes For Permit 04041477
Permit Number 04041477
Review Stop B
Sequence Number 2
Notes
Date Text
2004-07-21 00:00:00COMMENT #10 HAS BEEN DISCUSSED WITH THE
 ARCHITECT.OPENING PROTECTIVES ARE NOT
 REQUIRED.
 -
2004-07-15 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 5/19/04:
  
 1) INFORMATIVE:
 COMMENT RESPONSE DATED 6/15/04 IS NOTED.
 THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) INFORMATIVE:
 COMMENT RESPONSE DATED 6/15/04 IS NOTED.
 IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 4) FBC* 104.2.4SUBMIT A THIRD COPY OF
 THE SIGNED AND SEALED SURVEY DRAWING AND
 INSERT ONE COPY INTO EACH SET OF PLANS.
  
 6) FBC 13-103.1.2BEFORE A BUILDING
 PERMIT CAN BE ISSUED, SHEET 2 OF THE
 SUBMITTED ENERGY CODE COMPLIANCE FORMS
 SHALL BE SIGNED BY THE BUILDING OWNER,
 OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
 -ALSO, ADD THE OWNER'S NAME IN THE
 SPACE PROVIDED ON SHEET 1 OF THE FORM,
 -AND CORRECT THE OCCUPANCY CLASS TO
 'FACTORY/WAREHOUSE' (NOT 'ASSEMBLY') AS
 PER 'BUILDING DATA' ON SHEET SP-1.
  
 10) FBC 705.1.1.2OPENING PROTECTIVES.
 THE COMMENT RESPONSE IS NOTED BUT THE
 EXTERIOR WALL AT THE WEST END IS STILL
 LESS THAN 15 FEET FROM THE PROPERTY LINE
 SO THE OPENINGS SHALL BE PROVIDED WITH
 APPROVED OPENING PROTECTIVES (MIN 3/4 HR
 RATING, SEE FBC TABLE 705.1.2).AMEND
 THE PLANS TO DEMONSTRATE COMPLIANCE.
  
 12) PROVISO:
 SHELL BUILDING ONLY.THE BUILDING, AS
 CURRENTLY PROPOSED SHALL NOT BE
 OCCUPIED WITHOUT TENANT BUILD OUT TO
 ENSURE THE REQUIRED SANITARY PROVISIONS
 ARE MADE.
  
 13) PROVISO:
 TILT WALL PANELS.SUBMIT SHOP DRAWINGS
 PREPARED BY A FLORIDA REGISTERED
 ENGINEER AND REVIEWD BY THE ENGINEER OF
 RECORD, AS REFERENCED ON SHEET S-9.
  
 15) SUBMITTAL OF STATEWIDE PRODUCT
 APPROVAL COVER SHEETS IS NOTED BUT, LIKE
 THAT SUBMITTED FOR THE LOUVER DOOR, EACH
 ONE SHALL INCLUDE THE SUPPORTING
 EVALUATION/TEST REPORT DOCUMENT (E.G.
 MIAMI-DADE NOA) GIVING THE MAXIMUM
 TESTED SIZE, DESIGN PRESSURES AND
 INSTALLATION INSTRUCTIONS.THIS APPLIES
 TO THE SUBMITTED PRODUCT APPROVALS FOR
 BUILT-UP ROOFING, STOREFRONT WINDOWS,
 EXTERIOR DOORS AND SECTIONAL DOORS.
 REFER TO THE SUBMITTED PRODUCT APPROVAL
 FOR THE LOUVER DOOR WHICH INCLUDES THE
 REQUIRED SUPPORTING DOCUMENT.IF NOT
 FOUND ON THE DEPARTMENT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE, MIAMI-
 DADE PRODUCT CONTROL NOTICES OF
 ACCEPTANCE CAN BE DOWNLOADED FROM:
 WWW.MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH
 _APP.ASP
  
 18) SUBMIT THREE COPIES OF EACH PRODUCT
 APPROVAL.ONE COPY IS FOR THE RESIDENT
 INSPECTOR.
  
 19) REMOVE 'VOID' SHEETS FROM PLAN SETS.
 TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]