2004-05-24 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1) SHT P2.1 THE WATER RISER DIAGRAM DOES | | NOT REFLECT THE FLOOR PLAN. THE HOSE | | BIBB ON THE "G" COL. LINE IS NOT SHOWN | | ON THE RISER. SECTION 204.1.1 | | 2) SHT P2.1 WATER RISER DIAGRAM, AIR | | CHAMBERS ARE NOT APPROVED. IF WATER | | HAMMER ARRESTORS ARE USED THEY SHALL BE | | INSTALLED NEAR THE HOSE BIBBS, NOT IN | | THE CEILING PER PDI-WH 201. | | 3) SUBMIT CALCULATIONS FOR THE ROOF | | DRAINS PER SECTIONS 1106 & 1107 AND ALL | | SUBSECTIONS. SHOW SQUARE FEET OF ROOF | | AREA, AND SHOW 1/2 AREA OF ALL VERTICAL | | WALLS INCLUDING PARAPETS BEING ADDED TO | | ROOF AREA. | | 4) SHOW HIGH POINTS FOR ROOF GUTTER AND | | INDICATE SLOPE OF GUTTER PER TAB. 1106.6 | | 5) INDICATE TERMINATION OF DOWNSPOUTS | | FOR RAIN WATER. SECTION 1503.4.4 BLDG. | | CODE. | | 6) CIVIL SHEET ARE NOT SEALED AS REQUI- | | RED IN SECTION 104.2.2/FAC 61G15-23.002 | | (1) & FS 471.025. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|