Plan Review Notes
Plan Review Notes For Permit 04041477
Permit Number 04041477
Review Stop P
Sequence Number 1
Notes
Date Text
2004-05-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT P2.1 THE WATER RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. THE HOSE
 BIBB ON THE "G" COL. LINE IS NOT SHOWN
 ON THE RISER. SECTION 204.1.1
 2) SHT P2.1 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED. IF WATER
 HAMMER ARRESTORS ARE USED THEY SHALL BE
 INSTALLED NEAR THE HOSE BIBBS, NOT IN
 THE CEILING PER PDI-WH 201.
 3) SUBMIT CALCULATIONS FOR THE ROOF
 DRAINS PER SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. SHOW SQUARE FEET OF ROOF
 AREA, AND SHOW 1/2 AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPETS BEING ADDED TO
 ROOF AREA.
 4) SHOW HIGH POINTS FOR ROOF GUTTER AND
 INDICATE SLOPE OF GUTTER PER TAB. 1106.6
 5) INDICATE TERMINATION OF DOWNSPOUTS
 FOR RAIN WATER. SECTION 1503.4.4 BLDG.
 CODE.
 6) CIVIL SHEET ARE NOT SEALED AS REQUI-
 RED IN SECTION 104.2.2/FAC 61G15-23.002
 (1) & FS 471.025.
  
 REVIEW BY KEN STEVENS