2004-05-08 00:00:00********** UNSAT *****************
  
  
 1) NOTE: PLEASE SHOW ALL CONTINUOUS LOAD
 -S AT 125%(LIGHTING ETC)(LARGEST MOTORS)
 215.2,215.3,230.42,210.19A,210.20A ETC
  
 2)NOTE: PLEASE SEE ONE SET OF ELECTRICAL
 PLANS HAVE BEEN RETAINED. PLANS WILL NOW
 BE SENT TO FBPE'S FOR REVIEW ALONG WITH
 ALL PREVIOUS PLANS WHICH REQUIRE A
 LEGAL SIGNATURE FROM THE ENGINEER OF
 RECORD. INITIALS ARE NOT PERMITTED UNDER
 FS 471.025, FAC 61G15-23.002.
 A REVIEW OF PLANS AND DECISION BY THE
 FBPE'S WILL NOW BE REQUIRED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]