2004-05-17 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 3) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.SUBMIT A COPY OF THE 'UNITY
 OF TITLE' DOCUMENT SO THAT FBC TABLE 600
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
  
 4) FBC* 104.2.4SITE SURVEY.A SIGNED
 AND SEALED SURVEY DRAWING PREPARED BY A
 LICENSED SURVEYOR/MAPPER IS REQUIRED.
 (REF: 472.025(1) FL. STATUTES)
  
 5) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 6) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS.FOR
 SHELL BUILDINGS, FBC 13-101.1.6 REQUIRES
 THAT THE WHOLE BUILDING (INCL. FUTURE
 TENANT SPACE) BE CONSIDERED.SHELL
 BUILDINGS SHALL BE SHOWN TO COMPLY WITH
 METHOD B (SEE SUB-CHAPTER 4).ALL
 ASSUMPTIONS MADE ABOUT SYSTEMS, NOT
 SHOWN ON THE CURRENT PLANS, SHALL BE
 LISTED AND APPENDED TO THE FORM 400B FOR
 SUBMITTAL.THIS WILL BE COMPARED, AT A
 LATER DATE, TO THE ACTUAL SYSTEMS
 PROPOSED BY THE FUTURE TENANT(S).THE
 ASSUMPTIONS LISTED ON THE APPENDIX SHEET
 SHALL BE AT LEAST THE MINIMUM STANDARD
 (LIGHTING, HVAC ETC) TO ALLOW THE WHOLE
 BUILDING TO BE OCCUPIED FOR IT'S
 INTENDED PURPOSE.
  
 7) FBC* 105.3RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF
 THE RESIDENT INSPECTOR PROGRAM.A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED,
 ON THIS PROJECT, DUE TO ONE OR MORE OF
 THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
  
 8) THE 'WORTHINGTON RD' ADDRESS SHOWN ON
 THE TITLE BLOCK OF THE PLANS DOES NOT
 CORRESPOND WITH THE ADDRESS SHOWN ON THE
 PERMIT APPLICATION.CLARIFICATION/
 AMENDMENT IS REQUIRED.
  
 9) FBC 312.1STORAGE OCCUPANCY.THE
 PLANS SHALL BE AMENDED TO SPECIFICALLY
 STATE THE OCCUPANCY CLASSIFICATION AS
 'STORAGE' SO THAT THE REQUIREMENTS FOR
 HAZARDOUS OCCUPANCY MAY BE DEEMED NOT
 APPLICABLE.
  
 10) FBC 705.1.1.2OPENINGS IN WALLS
 WITHIN 15 FEET OF THE PROPERTY LINE
 SHALL BE EQUIPPED WITH APPROVED OPENING
 PROTECTIVES.THE EXTERIOR WALL AT THE
 WEST END IS LESS THAN 15 FEET FROM THE
 PROPERTY LINE.AMEND THE PLANS TO
 DEMONSTRATE COMPLIANCE.SEE ALSO THE
 ABOVE COMMENT REQUIRING SUBMITTAL OF A
 SURVEY DRAWING TO VERIFY SETBACKS
  
 11) FBC 1007STAIR CONSTRUCTION. SUBMIT
 DETAILS FOR THE EXTERIOR STAIR AND
 ASSOCIATED HANDRAILS AT THE WEST END OF
 THE BUILDING.
  
 12) PROVISO:
 SHELL BUILDING ONLY.THE BUILDING, AS
 CURRENTLY PROPOSED SHALL NOT BE OCCUPIED
 WITHOUT TENANT BUILD OUT TO ENSURE THE
 REQUIRED SANITARY PROVISIONS ARE MADE.
  
 13) PROVISO:
 TILT WALL PANELS.SUBMIT SHOP DRAWINGS
 PREPARED BY A FLORIDA REGISTERED
 ENGINEER AND REVIEWED BY THE ENGINEER OF
 RECORD, AS REFERENCED ON SHEET S-9.
  
 14) FBC 1501.1SHEET A-9, BUILT-UP
 ROOFING SYSTEM NOTE 07500.02.02 REFERS
 TO THE 'ROOFING SYSTEM REQUIREMENTS OF
 DADE COUNTY, FLORIDA'.THE ROOFING
 SYSTEM SHALL COMPLY WITH THE MINIMUM
 REQUIREMENTS OF SECTION 1501 OF THE
 FLORIDA BUILDING CODE 2001 AND THE
 STATED LIMITATIONS/INSTALLATION
 INSTRUCTIONS OF THE PRODUCT APPROVAL.
  
 15) SUBMIT PRODUCT APPROVALS FOR THE
 BUILT-UP ROOFING SYSTEM, STOREFRONT,
 MULLIONS, WINDOWS, EXTERIOR DOORS AND
 OVERHEAD DOORS.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
  
 16) PRODUCT APPROVAL.RULE 9B-72 FAC.
 FOR PRODUCTS WHICH DO NOT HAVE STATEWIDE
 PRODUCT APPROVAL, LOCAL PRODUCT APPROVAL
 CAN BE ACHIEVED IF THERE IS A QUALITY
 ASSURANCE PROGRAM IN PLACE WITH A STATE
 APPROVED QUALITY ASSURANCE ENTITY.IF
 NEITHER IS APPLICABLE, THEN SITE
 SPECIFIC APPROVAL IS REQUIRED.LOCAL
 PRODUCT APPROVAL WILL ALLOW A PRODUCT TO
 BE USED, IN ACCORDANCE WITH THE TEST
 CRITERIA, THROUGHOUT THE JURISDICTION OF
 WEST PALM BEACH.SITE SPECIFIC PRODUCT
 APPROVAL WILL ALLOW A PRODUCT TO BE
 USED ONLY ON THE PROJECT FOR WHICH THAT
 SITE SPECIFIC APPROVAL IS GRANTED.
 LOCAL AND SITE SPECIFIC PRODUCT APPROVAL
 APPLICATION FORMS ARE AVAILABLE FROM
 THIS OFFICE.APPROVED QUALITY ASSURANCE
 ENTITIES ARE LISTED ON THE DCA WEBSITE:
 WWW.FLORIDABUILDING.ORG/COMMON/C_ORG_
 REGI_SRCH.ASP
  
 17) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS