Plan Review Notes
Plan Review Notes For Permit 04041448
Permit Number 04041448
Review Stop M
Sequence Number 1
Notes
Date Text
2004-05-03 00:00:00DENIED:
 RETURN AIR REQUIRED FROM ROOMS THAT ARE
 SEPARATED BY DOORS.SEE THE ATTACHED
 SCHDEDULE FOR PROPER SIZING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved