Plan Review Notes For Permit 04041411 |
Permit Number |
04041411 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-04-26 00:00:00 | *************** UNSAT *************** | | | | 1)NOTE: PLEASE SEE FBC 104.2.1 | | PLANS MUST HAVE TH PRINTED NAME AND | | SIGNATURE OF THE PERSON RESPONSIBLE FOR | | DESIGN/PLANS. | | | | 2)NOTE: PLEASE SEE 210.52C1 FOR SPACING | | OF RECEPTS ALONG KITCHEN COUNTERSPACE. | | PLEASE SEE TWO COUNTER AREAS APPEAR TO | | BE OVER 4' AND ONLY ONE RECEPT SHOWN. | | | | 3)NOTE: PLEASE SEE 210.52 FOR RECEPT | | SPACING. 2', 6' RULE. | | PLEASE SEE BR#3, AND GRT RM. | | | | 4)NOTE: PLEASE SEE NEC ART 384 REFERENC- | | -ED ON PANEL SCHEDULE. 384 IS OUT OF THE | | 1999 NEC. AS OF 7/1/2003, THE STATE HAS | | ADOPTED THE 2002 NEC. THE ART # HAS | | CHANGED. | | | | PLEASE SEE ONE SET OF PLANS AHVE BEEN | | MNARKED UP FOR THE ABOVE AREAS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|