2004-04-26 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SEE FBC 104.2.1
 PLANS MUST HAVE TH PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 DESIGN/PLANS.
  
 2)NOTE: PLEASE SEE 210.52C1 FOR SPACING
 OF RECEPTS ALONG KITCHEN COUNTERSPACE.
 PLEASE SEE TWO COUNTER AREAS APPEAR TO
 BE OVER 4' AND ONLY ONE RECEPT SHOWN.
  
 3)NOTE: PLEASE SEE 210.52 FOR RECEPT
 SPACING. 2', 6' RULE.
 PLEASE SEE BR#3, AND GRT RM.
  
 4)NOTE: PLEASE SEE NEC ART 384 REFERENC-
 -ED ON PANEL SCHEDULE. 384 IS OUT OF THE
 1999 NEC. AS OF 7/1/2003, THE STATE HAS
 ADOPTED THE 2002 NEC. THE ART # HAS
 CHANGED.
  
 PLEASE SEE ONE SET OF PLANS AHVE BEEN
 MNARKED UP FOR THE ABOVE AREAS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  