Plan Review Notes For Permit 04041345 |
Permit Number |
04041345 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2004-11-10 00:00:00 | | | PROVISO | | ~~~~~~~ | | | | SEE COMMENTS NOT ADDRESSED FROM PREVIOUS | | REVIEW,ATTACHED. | | | | PLEASE SUBMIT DETAILS FOR THE PANEL | | SHOWN ON THE SCHEMATIC, FEEDER AND | | CONDUIT SIZE AND TYPE, PANEL RATING AND | | OCP, PANEL SCHEDULE AND COMPUTED LOAD, | | ETC. IF AN ELECTRIC HEATER IS TO BE | | INSTALLEDPLEASE SUBMIT CALCULATIONS | | FOR THE MAINSERVICE. | | | | SUBMIT THIS INFORMATION PRIOR TO | | CALLING ANY ELECTRICAL INSPECTIONS. | | | | ALLOW AT LEAST ONE WEEK FOR REVIEW. | | | | | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|