2006-06-16 00:00:00******* UNSAT 2ND REVIEW OF REVSION ***
  
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEW
 AND THIS REVIEW.
  
 1) NOTE: NOTE #1 NO, PLEASE SEE NUMEROUS
 ITEMS ARE STILL NOT CORRECT. PLEASE SEE
 LOADS EXCEEDING BRKR OCP, BLANK SPACES
 WITH LOADS, 50A BRKRS ON 1HP PUMPS, SEE
 PANEL "B" NOW SHOWS 24 AND 72 A'S ON TOW
 SEPARATE PHASES, #1'S ON RISER FOR
 FEEDERS, #6'S ON PANEL SCHEDULE ETC ETC.
 PLEASE SE MOST OF THESE ARE REDLINED ON
 PLANS.
 215.5,240.4,240.6,310.16, ETC
  
 ** PREVIOUS NOTE **
 PLEASE CORRELATE PANEL "B"
 LOADS, SIZE ETC. PLEASE SEE RISER SHOWS
 THIS AS 50A MLO, YET PANEL IS SHOWN AS
 100A MLO.
 PLEASE SEE LOAD ON PANEL "A" IS SHOWN AT
 72A'S WHICH FAR EXCEEDS THAT OF A 50A
 BRKR.
 240.4,310.16,215.5
  
 2) NOTE:NOTE #2 NO, SAME NOTE AND SAME
 AS NOTE #1.
 PLEASE SEE WATER HEATER IS NOW REMOVED
 FROM PANEL SCHEDULE YET LOAD IS STILL
 BEING SHOWN IN A BLANK SPACE??
 PLEASE STILL INDICATE ON SCHEDULE,
 HOWEVER IF IT IS GAS, THEN THERE IS NO
 LOAD.
  
 ** PREVIOUS NOTE**
 PLEASE CORRLEATE ALLLOADS AND
 ITEMS ON LOAD CALCULATIONS WITH THOSE ON
 PANEL SCHEDULES.
 PLEASE SEE THE MICRO/OVEN IS HSOWN WITH
 40A LOAD ON SCHEDULE, YET CALCS ONLY
 SHOW THIS AS 1.5KW??
 215.5
 PLEASE SEE COOKTOP WITH A HIGH LOAD, ON
 A 1-20A BRKR, YET CALCS SHOWS LOAD AT
 8KW. CORRELATE OCP, AWG AND LOADS.
 LABEL ACCORDINGLY.
 PLEASE SEE A GAS RANGE IS SHOWN ON LOAD
 CALCS.
 PLEASE SE WATER HEATER IS SHOWN AS GAS
 ON PANEL SCHEDULE, YET LOAD ON SCHEDULE
 DOES NOT CORRELATE WIHT THIS NOR DOES
 THE CALCULATIONS.
 215.5
  
 3) NOTE: NOTE #3, NO, PLEASE SEE
 DEN/STUDY WHICH STILL REQUIRES SOME SORT
 OF LT FIXTURE.
  
 ** PREVIOUS NOTE **
 PLEASE SEE REDLINED LOCATIONS
 FOR A MIN LT FIXTURE OF SOME TYPE WILL
 BE REQUIRED FOR EGRESS. NFPA-101, 7.8,
 NFPA-70 210.70, NFPA-101 CHAPTER 24
  
 4) NOTE: OK.
  
  
 5) NOTE:NOTE #5 NO,
  
  
 **PREVIOUS NOTE **
 PLEASE SEE ALL LIGHTING AND
 RECEPT CIRCUITS ON PANEL SCHEDULE SHALL
 BE SPECIFIC TO ROOM/AREA/LOCATION AND
 PURPOSE.
 PLEASE KNOW, IT IS NOT ACCEPTABLE TO
 JUST LIST ALL LIGHTING OR RECEPTS
 WITHOUT WHICH RM ETC THEY ARE FEEDING.
 IE; B-6 MASTER BDRM RECEPTS, FOYER LTS
 ETC.
  
 6) NOTE:OK
  
 NEW NOTE:
  
 7) NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) IS ATTACHED. IF PLANS COME
 BACK WITH ALL OF THESE ADDRESSED THE
 ABOVE SHALL BE IMPLEMENTED.
 PLEASE SEE THIS WILL BE THE 2ND SET
 RETAINED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]