2006-06-11 00:00:00 | ********* UNSAT ************* |
| |
| 1) NOTE: PLEASE CORRELATE PANEL "B" |
| LOADS, SIZE ETC. PLEASE SEE RISER SHOWS |
| THIS AS 50A MLO, YET PANEL IS SHOWN AS |
| 100A MLO. |
| PLEASE SEE LOAD ON PANEL "A" IS SHOWN AT |
| 72A'S WHICH FAR EXCEEDS THAT OF A 50A |
| BRKR. |
| 240.4,310.16,215.5 |
| |
| 2) NOTE: PLEASE CORRLEATE ALLLOADS AND |
| ITEMS ON LOAD CALCULATIONS WITH THOSE ON |
| PANEL SCHEDULES. |
| PLEASE SEE THE MICRO/OVEN IS HSOWN WITH |
| 40A LOAD ON SCHEDULE, YET CALCS ONLY |
| SHOW THIS AS 1.5KW?? |
| 215.5 |
| PLEASE SEE COOKTOP WITH A HIGH LOAD, ON |
| A 1-20A BRKR, YET CALCS SHOWS LOAD AT |
| 8KW. CORRELATE OCP, AWG AND LOADS. |
| LABEL ACCORDINGLY. |
| PLEASE SEE A GAS RANGE IS SHOWN ON LOAD |
| CALCS. |
| PLEASE SE WATER HEATER IS SHOWN AS GAS |
| ON PANEL SCHEDULE, YET LOAD ON SCHEDULE |
| DOES NOT CORRELATE WIHT THIS NOR DOES |
| THE CALCULATIONS. |
| 215.5 |
| |
| 3) NOTE: PLEASE SEE REDLINED LOCATIONS |
| FOR A MIN LT FIXTURE OF SOME TYPE WILL |
| BE REQUIRED FOR EGRESS. NFPA-101, 7.8, |
| NFPA-70 210.70, NFPA-101 CHAPTER 24 |
| |
| 4) NOTE: PLEASE SEE MANY LOCATIONS |
| REDLINED WHERE THE ENTIRE RECEPT IS |
| BEING SHOWN AS SWITCHED?? |
| PLEASE SEE THIS IS OK, IF INSTALLED THIS |
| WAY AS LONG AN ADDITIONAL RECEPT IS |
| ADDED TO MEET RECEPT SPACING PER 210.52 |
| |
| |
| 5) NOTE: PLEASE SEE ALL LIGHTING AND |
| RECEPT CIRCUITS ON PANEL SCHEDULE SHALL |
| BE SPECIFIC TO ROOM/AREA/LOCATION AND |
| PURPOSE. |
| PLEASE KNOW, IT IS NOT ACCEPTABLE TO |
| JUST LIST ALL LIGHTING OR RECEPTS |
| WITHOUT WHICH RM ETC THEY ARE FEEDING. |
| IE; B-6 MASTER BDRM RECEPTS, FOYER LTS |
| ETC. |
| |
| 6) NOTE: PLEASE VERIFY REDLINED AREA FOR |
| POSSIBLE GFI MISSING FOR PENINSULAR. |
| 210.52C1-5 |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |