2005-11-16 00:00:00 | *********** UNSAT *********** |
| |
| 1)NOTE: PLEASE SEE NUMEROUS RECEPTS |
| MISSING PER 210.52. |
| |
| 2)NOTE: PLEASE SEE 210.8A6, WHICH |
| REQUIRES ALL RECEPTS SERVING KITCHEN |
| COUNTERSPACE TO BE GFI/GFI PROTECTED. |
| |
| 3)NOTE: PLEASE SEE ALL OTHER RECEPTS |
| LOCATED WITHIN 6' OF OTHER SINLS OR |
| WETBAR LOCATIONS SHALL ALSO BE GFI/GFI |
| PROTECTED. |
| 210.8A7 |
| |
| 4)NOTE: PLEASE SEE MISSING RECEPTS PER |
| 210.52H? |
| |
| 5)NOTE: PLEASE SEE MISSING GFI RECEPTS |
| ALONG KITCHEN COUNTERSPACE, ISLAND ETC. |
| 210.52C1-C5 |
| |
| 6)NOTE: PLEASE SEE CLARIFY RISER DIAGRAM |
| GROUNDING ELECTRODE SYSTEM FROM MAIN |
| DISCONNECT AND THEN ALSO SHOWS A |
| GROUNDING ELECTRODE OF A "STEEL PIPE"?? |
| FROM METER. |
| PLEASE SEE 250.50, 250.6 AND 250.24 FOR |
| LOCATION OF GROUNDING ELECTRODE |
| CONDUCTOR, GROUNDING ELECTRODES ETC. |
| PLEASE VERIFY FIELD INSTALLATION. |
| |
| 7)NOTE: PLEASE CORRELATE LOAD |
| CALCULATIONS AND PANEL SCHEDULE FOR |
| COOK-TOP, RANGE, AND OVENS. |
| PLEASE SEE GAS, ELEC OR NOT SHOWN.?? |
| |
| 8)NOTE: PLEASE VERIFY 1HP PUMP WHICH |
| SHOWS 40A OCP?? AND #8 AWG?? |
| THIS DOES NOT SEEM TO BE CORRECT, PLEASE |
| SEE 430 FOR MAX OCP AND CODE LTR AND |
| TYPES OF MOTORS. |
| |
| 9)NOTE: PLEASE SEE 220.3B4. |
| PLEASE SHOW ALL RECESSED LTS BASED ON |
| MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| BE FIGURED IN W/ 3W/PER SQ FT. |
| PLEASE PROVIDE FIXTURE INFORMATION ON |
| LEGEND. |
| PLEASE REVISE LOAD CALCUALTIONS. |
| |
| ** PLEASE SUBMIT THE ABOVE INFORMATION |
| FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |