Plan Review Notes
Plan Review Notes For Permit 04041341
Permit Number 04041341
Review Stop E
Sequence Number 5
Notes
Date Text
2005-11-16 00:00:00*********** UNSAT ***********
  
 1)NOTE: PLEASE SEE NUMEROUS RECEPTS
 MISSING PER 210.52.
  
 2)NOTE: PLEASE SEE 210.8A6, WHICH
 REQUIRES ALL RECEPTS SERVING KITCHEN
 COUNTERSPACE TO BE GFI/GFI PROTECTED.
  
 3)NOTE: PLEASE SEE ALL OTHER RECEPTS
 LOCATED WITHIN 6' OF OTHER SINLS OR
 WETBAR LOCATIONS SHALL ALSO BE GFI/GFI
 PROTECTED.
 210.8A7
  
 4)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52H?
  
 5)NOTE: PLEASE SEE MISSING GFI RECEPTS
 ALONG KITCHEN COUNTERSPACE, ISLAND ETC.
 210.52C1-C5
  
 6)NOTE: PLEASE SEE CLARIFY RISER DIAGRAM
 GROUNDING ELECTRODE SYSTEM FROM MAIN
 DISCONNECT AND THEN ALSO SHOWS A
 GROUNDING ELECTRODE OF A "STEEL PIPE"??
 FROM METER.
 PLEASE SEE 250.50, 250.6 AND 250.24 FOR
 LOCATION OF GROUNDING ELECTRODE
 CONDUCTOR, GROUNDING ELECTRODES ETC.
 PLEASE VERIFY FIELD INSTALLATION.
  
 7)NOTE: PLEASE CORRELATE LOAD
 CALCULATIONS AND PANEL SCHEDULE FOR
 COOK-TOP, RANGE, AND OVENS.
 PLEASE SEE GAS, ELEC OR NOT SHOWN.??
  
 8)NOTE: PLEASE VERIFY 1HP PUMP WHICH
 SHOWS 40A OCP?? AND #8 AWG??
 THIS DOES NOT SEEM TO BE CORRECT, PLEASE
 SEE 430 FOR MAX OCP AND CODE LTR AND
 TYPES OF MOTORS.
  
 9)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 PLEASE REVISE LOAD CALCUALTIONS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]