2005-04-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT P-2 SANITARY RISER DIAGRAM DOES
 NOT MEET THE CODE REQUIREMENTS:
 A) SHOW ALL PIPE SIZES. SECTIONS
 104.2.1. AND TABLE 709.1
 B) RISER DIAGRAM INDICATES 2" PIPE TO
 WATER CLOSETS. PER TABLE 709.1 FOOTNOTE
 "D" TRAP SIZE SHALL BE CONSISTANT WITH
 FIXTURE OUTLET SIZE. MANUF.
 SPECIFICATION SHEETS WILL BE REQUIRED AT
 THE TIME OF PLUMBING FINAL SHOWING THE
 OUTLET SIZE OF WATER CLOSETS.
 C) WHITE OUT IS NOT APPROVED FOR SIGNED
 SEALED AND DATED PLANS. SECTION
 104.2.1.3.
 D) FITTING AT JUNCTION OF W/M AND
 UTILITY SINK DOES NOT COMPLY WITH
 SECTION 706.3. FITTING SHALL GUIDE
 SEWAGE IN DIRECTION OF FLOW.
 E) VENT FOR MASTER BATH WATER CLOSET
 APPEARS TO BE A DRY HORIZONTAL VENT
 WHICH IS NOT APPROVED PER SECTIONS 905.3
 AND 905.4.
  