Plan Review Notes For Permit 04041341 |
Permit Number |
04041341 |
|
Review Stop |
P |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2005-04-02 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1) SHT P-2 SANITARY RISER DIAGRAM DOES | | NOT MEET THE CODE REQUIREMENTS: | | A) SHOW ALL PIPE SIZES. SECTIONS | | 104.2.1. AND TABLE 709.1 | | B) RISER DIAGRAM INDICATES 2" PIPE TO | | WATER CLOSETS. PER TABLE 709.1 FOOTNOTE | | "D" TRAP SIZE SHALL BE CONSISTANT WITH | | FIXTURE OUTLET SIZE. MANUF. | | SPECIFICATION SHEETS WILL BE REQUIRED AT | | THE TIME OF PLUMBING FINAL SHOWING THE | | OUTLET SIZE OF WATER CLOSETS. | | C) WHITE OUT IS NOT APPROVED FOR SIGNED | | SEALED AND DATED PLANS. SECTION | | 104.2.1.3. | | D) FITTING AT JUNCTION OF W/M AND | | UTILITY SINK DOES NOT COMPLY WITH | | SECTION 706.3. FITTING SHALL GUIDE | | SEWAGE IN DIRECTION OF FLOW. | | E) VENT FOR MASTER BATH WATER CLOSET | | APPEARS TO BE A DRY HORIZONTAL VENT | | WHICH IS NOT APPROVED PER SECTIONS 905.3 | | AND 905.4. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|