Plan Review Notes For Permit 04041341 |
Permit Number |
04041341 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2005-03-03 00:00:00 | ******** PROVISO/NOTES *********** | | | | | | 1)NOTE: PLEASE SEE NOTE #5 FROM PREVIOUS | | REVIEW. | | PLEASE SEE 220.3B4. | | PLEASE SHOW ALL RECESSED LTS BASED ON | | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT | | BE FIGURED IN W/ 3W/PER SQ FT. | | PLEASE PROVIDE FIXTURE INFORMATION ON | | LEGEND. | | | | PLEASE REVISE ALONG WITH ANY OTHER | | CHANGES BEFORE ROUGH ELECTRICAL | | INSPECTION. | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | | PLEASE SEE 210.52D FOR BATH RECEPTS | | PLEASE SEE 210.52 MISSING BEDRM RECEPTS. | | | | BOTH OF THESE ITEMS REDLINED ON PLANS. |
|