2005-02-17 00:00:00THIRD MECH. REVIEW:
  
 1. RETURN AIR DUCT FROM BALLERY
 REFLECTS 16" THEN CHANGES TO 10" DUCT
 RETURNING TO A.H.U.#1 .
 PLEASE CORRECT.
 2. RETURN AIR DUCT FROM BEDROOM #3 NOT
 SIZED.
 3. RETURN AIR DUCT FROM BEDROOM #2 AND
 #3 REFLECT 10" RETURNING TO A.H.U.#1.
  
 PLEASE CORRECT R/A DUCT SIZE.
  
 4. AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIED PER 2001 FBC/M
 307.2.3 FOR A.H.U. .
  
 PAT RAFTER 561/805/6728 . PLEASE CALL
 IF THEAR ENY QUESTION.
  