2005-02-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT P-2 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, DOES NOT
 MEET CODE REQUIREMENTS, NOR IS IT DRAWN
 IN A CLEAR ISOMETRIC FORM.
 A) SEE EXAMPLE ON SHT P-2 IN RED INK
 THAT SHOWS PIPING THAT IS DRAWN IN THE
 VERTICLE INDICATES PIPING TO A SECOND
 FLOOR. AND SEE EXAMPLE OF REMDEDY FOR
 THE W/M, UTILITY SINK.
 B) ISOMETRIC IS A REVERSE OF THE FLOOR
 PLAN. SECTION 104.2.1.
 C) BATH #3 IS MISSING THE TUB ON THE
 SANT. RISER THAT IS SHOWN ON THE FLOOR
 PLAN. SECTION 104.2.1.
 D) UTILITY SINK IS NOT VENTED. SECTION
 901.2.1.
 E) WASH MACHINE REQUIRES A MIN. 2'
 STANDPIPE, AND A CLEANOUT 4' ABOVE THE
 FLOOR. SECTIONS 1002.1 & 708.10.
 F) TRAPS ARE REQUIRED ON ALL SHOWERS,
 TUBS, AND BIDET. SECTION 1002.1.
 G) THE AIR ADMITTENCE VALVE FOR THE
 ISLAND SINK IN THE KITCHEN SHALL BE
 SHOWN ON THE SANITARY RISER DIAGRA.
 SECTION 104.2.1. & SECTION 901.2.1.
  