Plan Review Notes For Permit 04041341 |
Permit Number |
04041341 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-02-16 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1) SHT P-2 SANITARY RISER DIAGRAM DOES | | NOT REFLECT THE FLOOR PLAN, DOES NOT | | MEET CODE REQUIREMENTS, NOR IS IT DRAWN | | IN A CLEAR ISOMETRIC FORM. | | A) SEE EXAMPLE ON SHT P-2 IN RED INK | | THAT SHOWS PIPING THAT IS DRAWN IN THE | | VERTICLE INDICATES PIPING TO A SECOND | | FLOOR. AND SEE EXAMPLE OF REMDEDY FOR | | THE W/M, UTILITY SINK. | | B) ISOMETRIC IS A REVERSE OF THE FLOOR | | PLAN. SECTION 104.2.1. | | C) BATH #3 IS MISSING THE TUB ON THE | | SANT. RISER THAT IS SHOWN ON THE FLOOR | | PLAN. SECTION 104.2.1. | | D) UTILITY SINK IS NOT VENTED. SECTION | | 901.2.1. | | E) WASH MACHINE REQUIRES A MIN. 2' | | STANDPIPE, AND A CLEANOUT 4' ABOVE THE | | FLOOR. SECTIONS 1002.1 & 708.10. | | F) TRAPS ARE REQUIRED ON ALL SHOWERS, | | TUBS, AND BIDET. SECTION 1002.1. | | G) THE AIR ADMITTENCE VALVE FOR THE | | ISLAND SINK IN THE KITCHEN SHALL BE | | SHOWN ON THE SANITARY RISER DIAGRA. | | SECTION 104.2.1. & SECTION 901.2.1. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] | | |
|