Plan Review Notes For Permit 04041341 |
Permit Number |
04041341 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-08-23 00:00:00 | ******** PROVISO/REVISION *********** | | | | 1)NOTE: PLEASE SEE THERE ARE NUMEROUS | | REFERENCES ON ELECTRICAL PLANS WHICH | | REF FBC AND ARTS:. PLEASE ADJUST TO NEC. | | | | 2)NOTE: PLEASE SEE FRIG IS NOW SHOWN AS | | A 2P20A FEED ON A SINGLE POLE SPACE. | | | | 3)NOTE: PLEASE ANY HANDDRAWN CHANGES TO | | PLANS MUST BE DONE BY ARCH OF RECORD. | | | | 4)NOTE: PLEASE SEE RISER DIAGRAM SHOWS | | PVC AND GR CONDUIT. | | | | 5)NOTE: PLEASE SEE 220.3B4. | | PLEASE SHOW ALL RECESSED LTS BASED ON | | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT | | BE FIGURED IN W/ 3W/PER SQ FT. | | PLEASE PROVIDE FIXTURE INFORMATION ON | | LEGEND. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW BEFORE ROUGH ELECTRICAL INSPECT- | | -ION IS CALLED IN. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | NOT ALL NOTES FROM FIRST REVIEW WERE | | ADDRESSED. | | SEE PROVISO ATTACHED TO PLANS. | | FEES WILL BE DUE FOR REVISION. | | IF PLANS COME BACK FOR ANY COMMENTS BY | | OTHER TRADES , PLEASE ADDRESS COMMENTS | | AT THIS TIME TO AVOID REVISIONS AT LATER | | DATE. | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 |
|