2004-08-23 00:00:00******** PROVISO/REVISION ***********
  
 1)NOTE: PLEASE SEE THERE ARE NUMEROUS
 REFERENCES ON ELECTRICAL PLANS WHICH
 REF FBC AND ARTS:. PLEASE ADJUST TO NEC.
  
 2)NOTE: PLEASE SEE FRIG IS NOW SHOWN AS
 A 2P20A FEED ON A SINGLE POLE SPACE.
  
 3)NOTE: PLEASE ANY HANDDRAWN CHANGES TO
 PLANS MUST BE DONE BY ARCH OF RECORD.
  
 4)NOTE: PLEASE SEE RISER DIAGRAM SHOWS
 PVC AND GR CONDUIT.
  
 5)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGH ELECTRICAL INSPECT-
 -ION IS CALLED IN.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 NOT ALL NOTES FROM FIRST REVIEW WERE
 ADDRESSED.
 SEE PROVISO ATTACHED TO PLANS.
 FEES WILL BE DUE FOR REVISION.
 IF PLANS COME BACK FOR ANY COMMENTS BY
 OTHER TRADES , PLEASE ADDRESS COMMENTS
 AT THIS TIME TO AVOID REVISIONS AT LATER
 DATE.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717