Plan Review Notes
Plan Review Notes For Permit 04041341
Permit Number 04041341
Review Stop E
Sequence Number 10
Notes
Date Text
2006-07-03 00:00:00******** UNSAT ***********
  
 1) NOTE: PLEASE SEE NUMEROUS ITEMS ON
 PANEL SCHEDULE AND LOCD CALCULATIONS
 WHICH STILL DO NOT CORRELATE.
 PLEASE SEE AHU'S, SPA, POOL, DISHWASHER
 (S), LAUNDRY/WASHER, ETC ETC.
 PLEASE SEE PANELS STILL DO NOT
 CORRELATE.
 215.5,240.4,310.16, ( 2002 NEC)
  
 2) NOTE: PLEASE SHOW EACH PANEL WITH
 CORRECT LOADS AND LOAD CALCULATIONS PER
 NEC 220.
 PLEASE SEE THE LOADS FOR "B".
  
 3) NOTE: PLEASE SEE MIN LT FIX REQUIRED
 FOR EGRESS. LS 101 7.8, 210.70
  
 4) NOTE: PLEASE SEE THAT THE RISER AND
 PANELS STILL DO NOT CORRELATE.
 LOADS DO NOT CORRELATE.
 215.5,310.16,240.4 ETC.
  
 *** IMPORTANT ***
  
 4) NOTE: PLEASE KNOW, ONE OF THE COPIES
 ARE RETAINED ONCE AGAIN. IF PLANS DO NOT
 COME BACK WITH ALL CORRECTIONS AS NOTED
 ON ALL PREVIOUS REVIEWS, A 4X FEE FOR
 THE PLAN REVIEW PORTION OF THE PERMIT
 FEE WILL BE ASSESSED AS REQUIRED PER FS
 553.80(2)(B) TO THE DESIGN PROFESSIONAL.
 PLEASE KNOW ALL PLANS RETAINED TO DATE
 WILL BE TURNED OVER THE STATE'S LEGAL
 COUNSEL TO THE FLORIDA BOARD OF
 ARCHITECT'S FOR PEIR REVIEW. PLEASE SEE
 FS 481.221(4)
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  