2006-07-03 00:00:00 | ******** UNSAT *********** |
| |
| 1) NOTE: PLEASE SEE NUMEROUS ITEMS ON |
| PANEL SCHEDULE AND LOCD CALCULATIONS |
| WHICH STILL DO NOT CORRELATE. |
| PLEASE SEE AHU'S, SPA, POOL, DISHWASHER |
| (S), LAUNDRY/WASHER, ETC ETC. |
| PLEASE SEE PANELS STILL DO NOT |
| CORRELATE. |
| 215.5,240.4,310.16, ( 2002 NEC) |
| |
| 2) NOTE: PLEASE SHOW EACH PANEL WITH |
| CORRECT LOADS AND LOAD CALCULATIONS PER |
| NEC 220. |
| PLEASE SEE THE LOADS FOR "B". |
| |
| 3) NOTE: PLEASE SEE MIN LT FIX REQUIRED |
| FOR EGRESS. LS 101 7.8, 210.70 |
| |
| 4) NOTE: PLEASE SEE THAT THE RISER AND |
| PANELS STILL DO NOT CORRELATE. |
| LOADS DO NOT CORRELATE. |
| 215.5,310.16,240.4 ETC. |
| |
| *** IMPORTANT *** |
| |
| 4) NOTE: PLEASE KNOW, ONE OF THE COPIES |
| ARE RETAINED ONCE AGAIN. IF PLANS DO NOT |
| COME BACK WITH ALL CORRECTIONS AS NOTED |
| ON ALL PREVIOUS REVIEWS, A 4X FEE FOR |
| THE PLAN REVIEW PORTION OF THE PERMIT |
| FEE WILL BE ASSESSED AS REQUIRED PER FS |
| 553.80(2)(B) TO THE DESIGN PROFESSIONAL. |
| PLEASE KNOW ALL PLANS RETAINED TO DATE |
| WILL BE TURNED OVER THE STATE'S LEGAL |
| COUNSEL TO THE FLORIDA BOARD OF |
| ARCHITECT'S FOR PEIR REVIEW. PLEASE SEE |
| FS 481.221(4) |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |