Plan Review Notes For Permit 04041341 |
Permit Number |
04041341 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-04-28 00:00:00 | DENIED: | | PLEASE PROVIDE THE FOLLOWING: | | | | 1.ENERGY & MANUAL J CALCULATIONS PER | | 2001 FBC CHAPTER 13, SUB-CHAPTER 6. | | | | 2.AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. |
|