Plan Review Notes
Plan Review Notes For Permit 04041341
Permit Number 04041341
Review Stop E
Sequence Number 1
Notes
Date Text
2004-04-26 00:00:00********** UNSAT ***********
  
 1)NOTE: PLEASE SEE NOTE:9 MENTIONS THAT
 ALL WIRE TO BEA MIN OF #12, YET PANELS
 SHOWS #14. PLEASE CORRELATE.
  
 2)NOTE: PLEASE SEE ALL NEC ARTS REFER-
 -ENCED ON PLANS MENTIONS PER FBC.
 THESE ARE 2002 NEC CODES.
  
 3)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 SYSTEM TO BLDG/FOOTER STEEEL, COLD
 WATER. 250.50
  
 4)NOTE: PLEASE SEE OCP ON PANEL SCHEDULE
 -S FOR ALL 220V ITEMS. THESE APPEAR TO
 BE MISPRINTS AND SHOW ALL AS 1-POLE
 BRKRS.
  
 5)NOTE: PLEASE SEE PANEL SCHEDULE AND
 RISER DIAGRAM. SHOWS 3#-? FOR CONDUCTORS
 TO SUB PANEL. PLEASE VERIFY AWG AND # OF
 CONDUCTORS.
 310.16, 215.5
  
 6)NOTE: PLEASE SEE NEC 220. PLEASE SHOW
 LOAD CALCULATIONS AS SET FORTH IN 220
 FOR MIN LOADS ETC. LOAD CALCULATIONS
 NEED TO BE SHOWN. 215.5
  
 7)NOTE: PLEASE SEE NFPA-72 8-1.4.2 FOR
 SD INSTALLATION. SD SHOWN OUTSIDE BEDRM
 #3/ KITCHEN MAY NEED TO BE MOVED.
 THIS IS JUST AN FYI.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]