Plan Review Notes
Plan Review Notes For Permit 04041338
Permit Number 04041338
Review Stop P
Sequence Number 1
Notes
Date Text
2004-05-03 00:00:00PLUMBING PLAN REVIEW, DENIED FBC 2001
 (1)SEC 104.6.5 BUILDING PERMIT VALUATION
 VALUATION BASED ON TOTAL REPLACEMENT VAL
 UE TO INCLUDE STRUCTAL, ELECTRIC,PLUMBIN
 G, MECHANICAL, INTERIOR FINISH, NORMAL
 SITE WORK, ARCHITECTURAL AND DESIGN FEES
 EXCLUDING ONLY LAND VALUE.
 (2) ADD THE FOLLOWING TO PLUMBING NOTES.
 SEC 424.2.6.6.5 WHERE PROVIDED, THE
 VACUM OR PRESSURE CLEANER FITTING SHALL
 BE LOCATED AT LEAST 6" AND NOT GREATER
 THAN 12" BELOW THE MINIMUM OPERATING
 WATER LEVEL,
 SEC 424.2.9 WATER SUPPLY, LOCAL ORDANCE
 #2853-95 BACK FLOW PREVENTER REQUIRED
 ON WATER SERVICE, PRIOR TO COMMENCING
 WORK.
 SEC 424.2.12.1 PRESSURE TEST. NO AIR
 TEST WILL BE APPROVED FOR PVC PIPE.
 SEC 424.2.13.2 JOINTS AND CONNECTIONS
 PURPLE PRIMER, REQUIRED ON PVC PIPING.
 SEC 424.2.14.2 WATER RETENTION, PROVIDE
 A POSITIVE MEANS OF RETAINING WATER IN
 THE HEATER WHEN THE PUMP IS SHUT OFF.
 SEC 424.2.14.4 CONNECTIONS, ALL WATER
 HEATING HEATING EQUIPMENT SHALL BE INSTA
 LLED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE WATER HEATER.
 SEC 424.2.15 GAS PIPING, SEPERATE PLANS
 AND PERMIT REQUIRED.
 END OF COMMENTS QUESTIONS 561-805-6692