2004-07-26 00:00:00DENIED:
 INSUFFICIENT INFORMATION, PLEASE PROVIDE
 THE FOLLOWING INFORMATION FOR COMPLIANCE
 WITH NFPA 33:
  
 1.INDICATE THE UTILIZATION OF THE
 SPRAY BOOTH.(AUTO, FURNITURE, ETC?)
  
 2.INDICATE CLEARANCE AROUND SPRAY
 BOOTH.
  
 3.PROVIDE DISTANCE FROM EXHAUST
 TERMINATION TO THE PROPERTY LINES &
 FRESH AIR INTAKES.
  
 4.INDICATE FRESH AIR MAKE UP.
  
 5.INDICATE STORAGE FOR COMBUSTIBLES.
  
 6.PROVIDE SPECIFICATION ON THE EXHAUST
 FAN(S).
  
 SHOW COMPLIANCE WITH NFPA 33 AND 34 IF
 APPLICABLE.
  