2004-07-26 00:00:00 | DENIED: | | INSUFFICIENT INFORMATION, PLEASE PROVIDE | | THE FOLLOWING INFORMATION FOR COMPLIANCE | | WITH NFPA 33: | | | | 1.INDICATE THE UTILIZATION OF THE | | SPRAY BOOTH.(AUTO, FURNITURE, ETC?) | | | | 2.INDICATE CLEARANCE AROUND SPRAY | | BOOTH. | | | | 3.PROVIDE DISTANCE FROM EXHAUST | | TERMINATION TO THE PROPERTY LINES & | | FRESH AIR INTAKES. | | | | 4.INDICATE FRESH AIR MAKE UP. | | | | 5.INDICATE STORAGE FOR COMBUSTIBLES. | | | | 6.PROVIDE SPECIFICATION ON THE EXHAUST | | FAN(S). | | | | SHOW COMPLIANCE WITH NFPA 33 AND 34 IF | | APPLICABLE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|