Plan Review Notes For Permit 04041316 |
Permit Number |
04041316 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-07-29 00:00:00 | 1) PLEASE PROVIDE FLOOR PLAN | | ILLUSTRATING WHERE SPRAY BOOTH WILL | | BE POSITIONED. | | | | 2) PLEASE DISPLAY THE REQUIRED THREE | | FOOT CLEARANCE FOR CLEANING PURPOSES | | AROUND THE BOOTH. | | | | 3) PLEASE INDICATE HOW BOOTH WILL | | BE GROUNDED AND BONDED. | | | | 4) NO MENTION ON HOW THE BOOTH WILL | | BE PROTECTED FROM FIRE. FIRE SPRINKLERS | | OR A DRY CHEMICAL SYSTEM WILL BE | | REQUIRED. | | | | 5) PLEASE PROVIDE DETAILS ON FILTERS. | | | | 6) PLEASE INDICATE EXHAUST DUCT LOCATION | | AND CFM OF FAN. | | | | 7) PLEASE EXPLAIN MAKE-UP AIR FOR | | BOOTH. | | | | 8) PLEASE PROVIDE MORE DETAILS ON | | ELECTRIC. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|