Plan Review Notes For Permit 04041316 |
Permit Number |
04041316 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-07-23 00:00:00 | *********** UNSAT ************ | | | | 1)NOTE: PLEASE SEE PLANS DO NOT INDICATE | | ANY ELECTRICAL? | | IS THERE GOING TO BE LTS? INSIDE UNIT, | | OUTSIDE UNIT? | | PLEASE SHOW AREA AND CLASS LOCATIONS | | AROUND BOOTH FOR WHICH PURPOSE IT WILL | | BE USED. | | PLEASE SEE NEC 516 FOR DEFINITION OF | | USES ALONG WITH NFPA WHICH WILL BE | | REFERENCED BY FIRE PLAN REVIEW. | | PLEASE INDICATE ALL REQUIRED UNDER 516. | | 2002 NEC. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|