Plan Review Notes
Plan Review Notes For Permit 04041242
Permit Number 04041242
Review Stop E
Sequence Number 2
Notes
Date Text
2004-06-22 00:00:00********** UNSAT 2ND TIME ********
  
 1)NOTE: PLEASE SEE MOST NOTES FROM FIRST
 REVIEW STILL NEED TO BE ADDRESSED.
  
 2 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 3)NOTE: PLEASE SEE CIRCUITING IS STILL
 NOT SHOWN ON PLANS AND NEEDS TO
 CORRELATE WITH SUBMITTED PANEL SCHEDULE.
  
 4)NOTE: PLEASE SEE PREVIOUS NOTES.
  
 5)NOTE: PLEASE SEE ATTACHED COPY OF
 FS 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL.
 THIS IS GIVEN AS A NOTICE ONLY.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING. ONE SET
 FO OLD SHEETS MAY BE SUBMITTED FOR
 REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]