2004-04-28 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| |
| 1) NEW TOILET ROOM SHALL COMPLY WITH |
| SECTIONS 11-4.16, 11-4.19, & 11-4.22 AND |
| ALL SUBSECTIONS. SUBMIT A DETAIL SHOWING |
| CLEAR FLOOR SPACE FOR W/C AND LAV, 5' |
| TURNING AREA, HEIGHT OF W/C, MEASUREMENT |
| OF WATER CLOSET AND LAV OFF WALL TO THE |
| CENTERLINE OF FIXTURES, HEIGHT OF LAV., |
| GRAB BAR HEIGHT/LENGTH ECT. |
| 2) SINK IN RECEPTIONIST AREA SHALL COMPY |
| WITH 11-4.24 AND ALL SUBSECTIONS. PROVI- |
| DE A DETAIL SHOWING ALL REQUIREMENTS. |
| 3) SHT 5 OF 5 SANITARY RISER DIAGRAM |
| DOES NOT MEET CODE REQUIREMENTS. SECTION |
| 909.1 ONLY THE FIXTURES WITHIN THE TOIL- |
| ET ROOM SHALL DRAIN THROUGH THE WET VENT |
| HORIZONTAL DRAIN. ALL OTHER FIXTURES |
| SHALL DISCHARGE DOWNSTREAM OF THE WET |
| VENTED TOILET ROOM FIXTURES. - D/TABLE |
| NOT VENTED. |
| 4) MORE INFORMATION REQUIRED FOR D/TABLE |
| PLEASE SUBMIT MANUF. INFORMATION FOR |
| THIS FIXTURE. SHOW APPROVAL BY AN APPRO- |
| VED TESTING AGENCY PER SECTION 303.2 & |
| 303.4 |
| 5) SHT 5 OF 5 PLUMBING RISER DIAGRAM, |
| MORE INFORMATION REQUIRED ON FIXTURE |
| SHOWN AFTER MASSAGE ROOM SINK. THIS FIX- |
| TURE IS NOT SHOWN ON FLOOR PLAN. PLEASE |
| CALRIFY. SECTION 104.2.1 |
| 6) A WATER RISER DIAGRAM IS REQUIRED PER |
| SECTION 104.3.1.1. INDICATE ALL WATER |
| HAMMER ARRESTORS REQUIRED BY SECTION |
| 604.9 TO BE LOCATED NEAR THE FIXTURE AS |
| REQUIRED IN PDI-WH 201 AND MANUF. INSTA- |
| LLATION INSTRUCTIONS. |
| 7) AN RPZ BACKFLOW IS REQUIRED ON WATER |
| SERVICE. |
| |
| REVIEW BY KEN STEVENS |