Plan Review Notes
Plan Review Notes For Permit 04041242
Permit Number 04041242
Review Stop P
Sequence Number 1
Notes
Date Text
2004-04-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) NEW TOILET ROOM SHALL COMPLY WITH
 SECTIONS 11-4.16, 11-4.19, & 11-4.22 AND
 ALL SUBSECTIONS. SUBMIT A DETAIL SHOWING
 CLEAR FLOOR SPACE FOR W/C AND LAV, 5'
 TURNING AREA, HEIGHT OF W/C, MEASUREMENT
 OF WATER CLOSET AND LAV OFF WALL TO THE
 CENTERLINE OF FIXTURES, HEIGHT OF LAV.,
 GRAB BAR HEIGHT/LENGTH ECT.
 2) SINK IN RECEPTIONIST AREA SHALL COMPY
 WITH 11-4.24 AND ALL SUBSECTIONS. PROVI-
 DE A DETAIL SHOWING ALL REQUIREMENTS.
 3) SHT 5 OF 5 SANITARY RISER DIAGRAM
 DOES NOT MEET CODE REQUIREMENTS. SECTION
 909.1 ONLY THE FIXTURES WITHIN THE TOIL-
 ET ROOM SHALL DRAIN THROUGH THE WET VENT
 HORIZONTAL DRAIN. ALL OTHER FIXTURES
 SHALL DISCHARGE DOWNSTREAM OF THE WET
 VENTED TOILET ROOM FIXTURES. - D/TABLE
 NOT VENTED.
 4) MORE INFORMATION REQUIRED FOR D/TABLE
 PLEASE SUBMIT MANUF. INFORMATION FOR
 THIS FIXTURE. SHOW APPROVAL BY AN APPRO-
 VED TESTING AGENCY PER SECTION 303.2 &
 303.4
 5) SHT 5 OF 5 PLUMBING RISER DIAGRAM,
 MORE INFORMATION REQUIRED ON FIXTURE
 SHOWN AFTER MASSAGE ROOM SINK. THIS FIX-
 TURE IS NOT SHOWN ON FLOOR PLAN. PLEASE
 CALRIFY. SECTION 104.2.1
 6) A WATER RISER DIAGRAM IS REQUIRED PER
 SECTION 104.3.1.1. INDICATE ALL WATER
 HAMMER ARRESTORS REQUIRED BY SECTION
 604.9 TO BE LOCATED NEAR THE FIXTURE AS
 REQUIRED IN PDI-WH 201 AND MANUF. INSTA-
 LLATION INSTRUCTIONS.
 7) AN RPZ BACKFLOW IS REQUIRED ON WATER
 SERVICE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]