Plan Review Notes For Permit 04041242 |
Permit Number |
04041242 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-04-21 00:00:00 | ************ UNSAT *************** | | | | 1)NOTE: PLEASE SHOW ALL MIN CIRCUITING | | REQ'D UNDER 2002 NEC AND CORRELATE WITH | | A PANEL SCHEDULE. PLEASE ALSO SHOW | | LOAD AND SIZE OF EXISITNG PANEL/SERVICE | | 215.5, 215.3, 230.42, 220. | | PLEASE ALSO SEE 700.12E FOR CIRCUITING | | OF EM/EXT LTS. | | | | 2)NOTE: PLEASE SEE 600.5 FOR NEW/EXIST- | | -ING REQ'D SIGN CIRCUIT. | | | | 3)NOTE: PLEASE SEE FS 471, NO HANDDRAWN | | CHANGES ARE TO BE MADE TO SIGNED AND | | SEALED PLANS W/OUT ENGINEER. | | | | 4)NOTE: PLEASE SEE NEC 517 FOR ALL | | REQ'D ITEMS TO BE LISTED ON PLANS. | | PLANS APPEAR TO SHOW TREATMENT AREAS | | THAT MAY MEET PARTS OF 517. | | 517.2, 517.60 PLEASE PROVIDE ADDITIONAL | | INFORMATION FOR THE ABOVE. | | | | 5)NOTE: PLEASE SEE COMMENTS FROM OTHER | | REVIEWERS THAT MAY HAVE AN AFFECT ON | | ELECTRICAL PLANS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|