Plan Review Notes
Plan Review Notes For Permit 04041180
Permit Number 04041180
Review Stop E
Sequence Number 4
Notes
Date Text
2005-06-14 00:00:00************* UNSAT ****************
  
 PLEASE SEE THE FOLLOWING NOTES FOR THE
 GENERATOR WHICH CAME IN AS A REVISIONS
 UNDER THE MAIN BLDG PERMIT..
  
  
 1)NOTE: PLEASE SUBMIT FOR SEPARATE
 GENERATOR PERMIT.
 PLEASE SUPPLY A COMPLETE RISER DIAGRAM
 ON HOW GENERATOR WILL BE WIRED INOT NEW
 ELECTRICAL SERVICE. WIRING DIAGRAM FROM
 MANUFACTURE SUBMITED DOES NOT MEET NEC.
  
 PLEASE SEE 225.31-225.36
  
 2)NOTE: PLEASE SUBMIT LOAD CALCAULTIONS
 FOR SERVICE. PLEASE SEE 702.5 AND
 220.31B FOR SIZING OF GEN FOR SERVICE.
  
 3)NOTE: PLEASE SEE PLANS ARE NOT
 REQUIRED TO BE DONE BY AND ARCH OR
 ENGINEER BUT HOWEVER THEY MAY BE DONE BY
 THEM ALSO.
 PLEASE SEE FBC 104.2.1 WHICH REQUIRES
 THE PRINTED NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR PLANS AND DESIGN.
 PLEASE NOTE: PLANS FOR EXISTING HOUSE
 ADDITION PERMIT WILL BE REQUIRED TO BE
 REVISED TO INCLUDE GEN WORK, HOWEVER
 THIS REVSION OF WORK MUST BE DONE BY THE
 ARCH OR ENGINEER OF RECORD.
 PER FS 481,471
 PLEASE SEE "PROVISO" GIVEN UPON ISSUANCE
 OF PERMIT HAS NOT BEEN REVISED AND OR
 CORRECTED AS OF THIS REVIEW.
  
 4)NOTE: PLEASE BE SURE THE GAS PERMIT IS
 EITHER APPLIED FOR OR REVISED IF ONE
 ALREADY EXISTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  