2005-06-14 00:00:00 | ************* UNSAT **************** |
| |
| PLEASE SEE THE FOLLOWING NOTES FOR THE |
| GENERATOR WHICH CAME IN AS A REVISIONS |
| UNDER THE MAIN BLDG PERMIT.. |
| |
| |
| 1)NOTE: PLEASE SUBMIT FOR SEPARATE |
| GENERATOR PERMIT. |
| PLEASE SUPPLY A COMPLETE RISER DIAGRAM |
| ON HOW GENERATOR WILL BE WIRED INOT NEW |
| ELECTRICAL SERVICE. WIRING DIAGRAM FROM |
| MANUFACTURE SUBMITED DOES NOT MEET NEC. |
| |
| PLEASE SEE 225.31-225.36 |
| |
| 2)NOTE: PLEASE SUBMIT LOAD CALCAULTIONS |
| FOR SERVICE. PLEASE SEE 702.5 AND |
| 220.31B FOR SIZING OF GEN FOR SERVICE. |
| |
| 3)NOTE: PLEASE SEE PLANS ARE NOT |
| REQUIRED TO BE DONE BY AND ARCH OR |
| ENGINEER BUT HOWEVER THEY MAY BE DONE BY |
| THEM ALSO. |
| PLEASE SEE FBC 104.2.1 WHICH REQUIRES |
| THE PRINTED NAME AND SIGNATURE OF THE |
| PERSON RESPONSIBLE FOR PLANS AND DESIGN. |
| PLEASE NOTE: PLANS FOR EXISTING HOUSE |
| ADDITION PERMIT WILL BE REQUIRED TO BE |
| REVISED TO INCLUDE GEN WORK, HOWEVER |
| THIS REVSION OF WORK MUST BE DONE BY THE |
| ARCH OR ENGINEER OF RECORD. |
| PER FS 481,471 |
| PLEASE SEE "PROVISO" GIVEN UPON ISSUANCE |
| OF PERMIT HAS NOT BEEN REVISED AND OR |
| CORRECTED AS OF THIS REVIEW. |
| |
| 4)NOTE: PLEASE BE SURE THE GAS PERMIT IS |
| EITHER APPLIED FOR OR REVISED IF ONE |
| ALREADY EXISTS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |