2004-08-19 00:00:00 | ********** UNSAT ************** |
| |
| ** PLEASE SEE SOME NOTES FROM FIRST |
| REVIEW STILL NEED TO BE ADDRESSED.** |
| |
| 1)NOTE: NOTE#1 NO. |
| PLEASE SEE LOAD CALCULATIONS WERE |
| SUBMITTED HOWEVER THEY DO NOT MEET NEC |
| 220.31B. |
| PLEASE ALSO SEE A/C LOAD IS BEING FIG |
| AS LIGHTING LOAD? |
| PLEASE SEE LOAD CALCS ONLY INCLUDE |
| NEW A/C AND NOT NEW AND EXSITING?? |
| |
| 2)NOTE: NOTE #2 NO. NO PANEL SCHEDULE |
| SUBMITTED SHOWING MIN CIRCUITS. |
| NOTES WERE SUBMITTED FOR NEW CIRCUITS, |
| HOWEVER PLEASE SEE THE FOLLOWING FOR |
| CORRECT LOADS, OCP AND AWG. |
| 210.52D,210.11C3 FOR BATHS.REQUIRED TO |
| BE 20A #12 ETC. |
| PLEASE SEE 210.12 FROM 2002 NEC FOR ARC- |
| -FAULT PROTECTION. PLANS INDICATE LIGHT- |
| -ING TO BE PROTECTED.?? SD'S RECEPTS, |
| LTS. |
| PLEASE SEE NO OCP/AWG FOR NEW A/C SHOWN? |
| |
| 3)NOTE: NOTE #3 OK. |
| |
| 4)NOTE: NOTE #4 NO. PLEASE SEE FBC |
| CHAPTER 34. 3401.7.1.1.2,3401.7.1.2.1 |
| PLEASE SHOW ALL EXISTING AREAS TO MEET |
| ABOVE PER ABOVE REQUIREMENTS. |
| |
| 5)NOTE: PLEASE SEE ATTACHED COPY OF |
| FS 553.80(2)(B) WITH RESPECT TO DESIGN |
| PROFESSIONAL. |
| THIS IS ONLY A NOTICE GIVEN AT THIS TIME |
| |
| 6)NOTE: PLEASE SEE 210.63 FOR LT REQ'D |
| FOR AHU IN MECH CLOSET.(NEW NOTE) |
| |
| |
| **PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| AND ONLY INSERT NEW SHEETS INTO COMPLETE |
| SETS FOR REVIEW AND STAMPING. |
| ONE SET OF EACH "OLD" SETS SHOULD BE |
| SUBMITTED FOR REFERENCE. **** |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |