Plan Review Notes
Plan Review Notes For Permit 04041180
Permit Number 04041180
Review Stop E
Sequence Number 2
Notes
Date Text
2004-08-19 00:00:00********** UNSAT **************
  
 ** PLEASE SEE SOME NOTES FROM FIRST
 REVIEW STILL NEED TO BE ADDRESSED.**
  
 1)NOTE: NOTE#1 NO.
 PLEASE SEE LOAD CALCULATIONS WERE
 SUBMITTED HOWEVER THEY DO NOT MEET NEC
 220.31B.
 PLEASE ALSO SEE A/C LOAD IS BEING FIG
 AS LIGHTING LOAD?
 PLEASE SEE LOAD CALCS ONLY INCLUDE
 NEW A/C AND NOT NEW AND EXSITING??
  
 2)NOTE: NOTE #2 NO. NO PANEL SCHEDULE
 SUBMITTED SHOWING MIN CIRCUITS.
 NOTES WERE SUBMITTED FOR NEW CIRCUITS,
 HOWEVER PLEASE SEE THE FOLLOWING FOR
 CORRECT LOADS, OCP AND AWG.
 210.52D,210.11C3 FOR BATHS.REQUIRED TO
 BE 20A #12 ETC.
 PLEASE SEE 210.12 FROM 2002 NEC FOR ARC-
 -FAULT PROTECTION. PLANS INDICATE LIGHT-
 -ING TO BE PROTECTED.?? SD'S RECEPTS,
 LTS.
 PLEASE SEE NO OCP/AWG FOR NEW A/C SHOWN?
  
 3)NOTE: NOTE #3 OK.
  
 4)NOTE: NOTE #4 NO. PLEASE SEE FBC
 CHAPTER 34. 3401.7.1.1.2,3401.7.1.2.1
 PLEASE SHOW ALL EXISTING AREAS TO MEET
 ABOVE PER ABOVE REQUIREMENTS.
  
 5)NOTE: PLEASE SEE ATTACHED COPY OF
 FS 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL.
 THIS IS ONLY A NOTICE GIVEN AT THIS TIME
  
 6)NOTE: PLEASE SEE 210.63 FOR LT REQ'D
 FOR AHU IN MECH CLOSET.(NEW NOTE)
  
  
 **PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE SET OF EACH "OLD" SETS SHOULD BE
 SUBMITTED FOR REFERENCE. ****
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]