Plan Review Notes
Plan Review Notes For Permit 04041180
Permit Number 04041180
Review Stop E
Sequence Number 1
Notes
Date Text
2004-04-21 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SEE 220.3C1, PLEASE
 PROVIDE COMPLETE LOAD CALCAULTIONS FOR
 NEW AND EXSITING.
 PLEASE CORRELATE SQ FT BEING ADDED,
 THERE ARE MORE THEN ONE PLACE ON PLANS
 WHERE SQ FT #'S DO NOT CORRELATE.
  
 2)NOTE: PLEASE SHOW/LIST PANEL SCHEDULE
 AND SHOW MIN CIRCUIT(S) FOR BATH AND
 ARC FAULT PROTECTED CIRCUIT(S) 210.12
  
 3)NOTE: PLEASE SEE RISER DIAGRAM, NOTES
 MENTIONS: 150A PANEL W/ 150A MCB, YET
 PANEL IS SHOWN AT 200A'S WITH 3/0'S
 AS SEC'S. PLEASE VERIFY.
  
 4)NOTE: PLEASE SEE FBC CHAPTER 34
 PLEASE SUBMIT ELECTRICAL PLANS SHOWING
 ALL EXISTING MEETING CODE AND OR ELEC-
 -TRICAL TO MEET CODE COMPLIANCE TO THE
 2002 NEC. PLEASE ALSO SEE NFPA-72
 FOR SD'S.
 ADDITIONS OF MORE THAN 25%.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]