2004-06-25 00:00:00 | **** UNSAT **** |
| |
| 1)NOTE: PLEASE SEE A NEW ELECTRICAL |
| WIRING DIAGRAM IS NOW BEING SUBMITTED |
| FOR REVIEW. NOTES ARE NOT THE SAME AS |
| PREVIOUS REVIEWS.PLEASE SEE NEW NOTES. |
| |
| 2)NOTE: PLEASE SEE DIAGRAM IS MISSING |
| WIRE SIZES FOR HEAT PUMP. |
| |
| 3)NOTE: PLEASE SEE NEW DIAGRAM IS NOW |
| ALSO SHOWING A NEW ELECTRICAL PANEL |
| FROM EXSITING. PLEASE INDICATE WIRE |
| SIZES, FEEDERS ETC. PLEASE SHOW SIZE |
| OF PANLE AND SIZE OF OCP FEEDING PANEL. |
| |
| 4)NOTE: PLEASE SEE HEAT PUMP IS A |
| CONTINUOUS LOAD WHICH SHOULD BE SHOWN |
| AT 125%. 215.3,220.19,230.42 ETC. |
| |
| 5)NOTE: PLEASE SEE 220.16 FOR LAUNDRY |
| CIRCUIT TO BE A MIN OF 1.5KW. |
| |
| DUE TO COMMENTS NOT BEING THE SAME FOR |
| ELECTRICAL AN ADDTIONL 4X FEE WILL NOT |
| BE ACCESSED FOR ELECTRICAL. |
| PLEASE SEE COMMENTS FROM PLUMB PLAN |
| REVIEWER REMAIN THE SAME AND COULD HAVE |
| ADDITONAL 4X FEE ACCESSED. PLEASE SEE |
| PLUMB COMMENTS. SAME PLANS CAME BACK FOR |
| REVIEW. NO NEW SHEETS SUBMITTED. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |