2004-06-25 00:00:00**** UNSAT ****
  
 1)NOTE: PLEASE SEE A NEW ELECTRICAL
 WIRING DIAGRAM IS NOW BEING SUBMITTED
 FOR REVIEW. NOTES ARE NOT THE SAME AS
 PREVIOUS REVIEWS.PLEASE SEE NEW NOTES.
  
 2)NOTE: PLEASE SEE DIAGRAM IS MISSING
 WIRE SIZES FOR HEAT PUMP.
  
 3)NOTE: PLEASE SEE NEW DIAGRAM IS NOW
 ALSO SHOWING A NEW ELECTRICAL PANEL
 FROM EXSITING. PLEASE INDICATE WIRE
 SIZES, FEEDERS ETC. PLEASE SHOW SIZE
 OF PANLE AND SIZE OF OCP FEEDING PANEL.
  
 4)NOTE: PLEASE SEE HEAT PUMP IS A
 CONTINUOUS LOAD WHICH SHOULD BE SHOWN
 AT 125%. 215.3,220.19,230.42 ETC.
  
 5)NOTE: PLEASE SEE 220.16 FOR LAUNDRY
 CIRCUIT TO BE A MIN OF 1.5KW.
  
 DUE TO COMMENTS NOT BEING THE SAME FOR
 ELECTRICAL AN ADDTIONL 4X FEE WILL NOT
 BE ACCESSED FOR ELECTRICAL.
 PLEASE SEE COMMENTS FROM PLUMB PLAN
 REVIEWER REMAIN THE SAME AND COULD HAVE
 ADDITONAL 4X FEE ACCESSED. PLEASE SEE
 PLUMB COMMENTS. SAME PLANS CAME BACK FOR
 REVIEW. NO NEW SHEETS SUBMITTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  