Plan Review Notes
Plan Review Notes For Permit 04041067
Permit Number 04041067
Review Stop E
Sequence Number 2
Notes
Date Text
2004-05-24 00:00:00********* UNSAT ****************
  
 1)NOTE: PLEASE SEE NOTES FROM FIRST
 REVIEW.
 PLEASE CORRELATE WIRING DIAGRAM WHICH
 SHOWS ALL EQUIPMENT BEING INSTALLED.
  
 2)NOTE: PLEASE SEE COPY OF FS 553.80(2)
 (B).THIS IS GIVEN WITH RESPECT TO THE
 DESIGN PROFESSIONAL.
  
 3)NOTE: PLEASE SEE LOAD CALCULATION
 SUBMITTED. PLEASE CORRELATE LOAD SHOWN
 ON HEAT PUMP WITH LOAD CALCS.
 PLEASE SEE 220.16 FOR MIN LAUNDRY/WASHER
 LOAD TO BE 1500 W.
  
  
 PLEASE INCLUDE SPECS FOR HEAT PUMP.
 CIRCLE OR LABEL UNIT/MODEL TO BE USED.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]