2004-05-03 00:00:00********* UNSAT ***************
  
 1)NOTE: PLEASE CORRELATE PLANS.
 PLANS CALL FOR HEAT PUMP , BLOWER ETC,
 YET WIRING DIAGRAM DOES NOT REFLECT ALL
 EQUIPMENT?
  
 2)NOTE: PLEASE SEE LOAD CALCS SUBMITTED,
 MENTIONS TWO LTS? ONLY ONE SHOWN ON PLAN
 -S??
  
 3)NOTE:MIN KW FOR LAUNDRY LOAD IS 1.5KW
 220.16B
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  