Date |
Text |
2004-04-26 00:00:00 | CHECKLIST FOR BUILDING REVIEW: |
| 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 2-SEC. 1005.4.4 FBC 2001 REQUIRES 24"MIN |
| CLEAR WINDOW OPENING IN HEIGHT. SH24 |
| AND SH34 ARE TYPICALLY 48" HEIGHT IN |
| WINDOW FRAME. A)SPECIFY WHICH SIZE OF |
| "SIMONTON" WINDOWS IS GOING TO BE USED |
| TO MEET THIS REQUIREMENTS. SEE WINDOW |
| DIMENSIONS ON PRODUCT APPROVAL AND |
| REVISE PLANS AS REQUIRED. |
| B)ALSO, WINDOWS SHOWN ON REAR ELEVATION |
| AREN'T DRAWN TO SCALE. THEY SCALE TO |
| BE LIKE SH25 OR SH35 WINDOWS. CLARIFY. |
| 3-SPECIFY SIZE OF ATTIC ACCESS AS REQ'D |
| BY SEC. 2309.6 FBC 2001. |
| 4-PLANS ARE MISSING ALL THE ENGINEER'S |
| INFORMATION AS REQ'D BY CHAPTER 471 |
| FLORIDA STATUTES. |
| 5-SHEET #7: REVISE MIN. SIZE FOR ATTIC |
| ACCESS. SEE SEC. 2309.6 FBC 2001. |
| 6-CEILING FAN CREDIT IS TAKEN ON THE |
| ENERGY CALCS. THEREFORE, SPECIFY |
| ON PLANS SIZE OF FAN REQUIRED AT EACH |
| ROOM. TABLE 6-6 CHAPTER 13 FBC 2001. |
| 7-NEED PRODUCT APPROVAL FOR ENTRY DOOR |
| WITH TRANSOM ABOVE SINGLE ASSEMBLY AS |
| SHOWN ON PLANS. |
| 8-NEED PRODUCT APPROVAL FOR GARAGE DOOR |
| THAT MEETS THE DESIGN PRESSURES THAT |
| WERE CALCULATED BY THE ENGINEER. |
| 9-SHEET #3A: A)ROOF FRAMING PLAN CALLS |
| FOR CONNECTOR A5 BUT TRUSS ANCHOR |
| SCHEDULE DOESN'T HAVE A5 CONNECTOR. |
| SPECIFY/CLARIFY AS REQUIRED. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| B)STUCCO NOTE NEED TO ADDRESS MIN. 7/8" |
| STUCCO THICKNESS AT FRAMED WALLS AS |
| REQ'D BY ASTM C-926. |
| 10-THIS BUILDING PERMIT APPLICATION IS |
| FOR LOT 48. IMPACT FEES STAMP CALLS |
| FOR LOT 12. REVISE/CLARIFY AS REQUIRED |
| |