Plan Review Notes For Permit 04040818 |
Permit Number |
04040818 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-04-26 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES. | | | | 1) SHT 2 AIR CHAMBERS NOT APPROVED. SEE | | SECTION 604.9 WATER HAMMER ARRESTORS | | WHERE REQUIRED, PDI-WH 201 AND MANUF. | | INSTALLATION INSTRUCTIONS FOR LOCATION. | | NOT IN CEILING. | | 2) NOT ALL SIGNATURES ARE THE SAME ON | | THE SEAL. NOT ALL SEALS READABLE. | | NOT ALL SHEETS SIGNED AND SEALED. | | TITLE BLOCK REQUIRES A SPACE FOR ARCHIT- | | ECTS PRINTED NAME.FAC-61G1-16.002 -003 | | -004. FS481.2055 | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|